Omron G3PE Three Phase Series Solid State Relay, 45 A Load, DIN Rail Mount, 528 V ac Load, 30 V dc Control
- RS Stock No.:
- 828-6906
- Mfr. Part No.:
- G3PE-545B-3N DC12-24
- Manufacturer:
- Omron
3 In stock for delivery within 1 working days
Added
Price Each
Was SGD524.34
You pay
SGD498.12
(exc. GST)
SGD542.95
(inc. GST)
Units | Per unit |
1 + | SGD498.12 |
- RS Stock No.:
- 828-6906
- Mfr. Part No.:
- G3PE-545B-3N DC12-24
- Manufacturer:
- Omron
Technical data sheets
Legislation and Compliance
- COO (Country of Origin):
- JP
Product Details
G3PE Series
Omron G3PE Series solid state relays with heat sinks for a wide range of applications.
Models also available with no zero cross
Compact with a slim profile
Improved surge dielectric strength for output circuits
Screw and DIN track mounting possible
RoHS compliant
Compact with a slim profile
Improved surge dielectric strength for output circuits
Screw and DIN track mounting possible
RoHS compliant
G3PE-545B-3N DC12-24 SSR – Compact 3-Phase Solid State Relay.
The G3PE SSR – Solid State Relay series have a slim compact design complete with built-in heat sinks. Solid state contactors for 3-phase heaters, reduced installation and available to DIN rail mount or screw mount. RoHS compliant with surge protection.
Features and Benefits of G3PE-545B-3N DC12-24 Compact SSR – Solid State Relay.
Three-phase.
Phototriac coupler.
Yellow indicator.
Rated input voltage 12 to 24 V dc.
Zero cross function.
DIN Rail Mounting available
Applicable load 45 A, 200 to 480 V ac. (dependent upon the ambient temperature).
3 Poles.
Built-in heat sink.
Phototriac coupler.
Yellow indicator.
Rated input voltage 12 to 24 V dc.
Zero cross function.
DIN Rail Mounting available
Applicable load 45 A, 200 to 480 V ac. (dependent upon the ambient temperature).
3 Poles.
Built-in heat sink.
SSR – Solid State Relay Input Rating at 25°C.
Operating voltage range 9.6 to 30 V dc.
Rated input current 10 mA max. (24 V dc).
Must operate voltage 9.6 V dc max.
Must release voltage 1 V dc max.
Rated input current 10 mA max. (24 V dc).
Must operate voltage 9.6 V dc max.
Must release voltage 1 V dc max.
SSR – Solid State Relay Output.
Rated load voltage 200 to 480 V ac, 50 / 60 Hz.
Load voltage range 180 to 528 V ac, 50 / 60 Hz.
Applicable load current 45 A at 25°C. (dependent upon the ambient temperature).
Load current minimum 0.5 A.
Inrush current 440 A, 60 Hz, 1 cycle. Peak value.
Resistive load 37.4 kW at 480 V ac.
Load voltage range 180 to 528 V ac, 50 / 60 Hz.
Applicable load current 45 A at 25°C. (dependent upon the ambient temperature).
Load current minimum 0.5 A.
Inrush current 440 A, 60 Hz, 1 cycle. Peak value.
Resistive load 37.4 kW at 480 V ac.
Additional Features G3PE-545B-3N DC12-24 Compact SSR 3-Phase SSR – Solid State Relay.
Operate and release time load power source cycle + 1 ms max.
Output ON voltage drop 1.8 V (RMS) max.
Leakage current 20 mA max at 480 v ac.
Vibration resistance 10 to 55 to 10 Hz, 0.175 single amplitude, 0.35 mm double amplitude – DIN rail mounted.
Vibration resistance 10 to 55 to 10 Hz, 0.375 single amplitude, 0.75 mm double amplitude – Screw mounted.
Shock resistance destruction 294 m/s² (reverse mount 98 m/s²).
Operating temperature – ambient -30°C to 80°C, no icing or condensation.
Relay weight 2 kg.
Output ON voltage drop 1.8 V (RMS) max.
Leakage current 20 mA max at 480 v ac.
Vibration resistance 10 to 55 to 10 Hz, 0.175 single amplitude, 0.35 mm double amplitude – DIN rail mounted.
Vibration resistance 10 to 55 to 10 Hz, 0.375 single amplitude, 0.75 mm double amplitude – Screw mounted.
Shock resistance destruction 294 m/s² (reverse mount 98 m/s²).
Operating temperature – ambient -30°C to 80°C, no icing or condensation.
Relay weight 2 kg.
What does Zero Cross Function mean in SSR in Solid State Relays?
Zero cross function will allow the relay to turn ON when the AC load power supply approaches 0 V suppressing any noise generated with a sudden load current increase. Zero cross function is effective across 2 types of noise, noise on power lines and noise emitted into open space.
Standards
UL508, CSA22.2 No.14, EN 60947-4-3.
Specifications
Attribute | Value |
---|---|
Maximum Load Current | 45 A |
Mounting Type | DIN Rail |
Maximum Load Voltage | 528 V ac |
Minimum Load Voltage | 180 V ac |
Maximum Control Voltage | 30 V dc |
Minimum Control Voltage | 9.6 V dc |
Switching Type | Zero Cross |
Control Voltage Range | 9.6 → 30 V dc |
Minimum Load Current | 0.5 A |
Terminal Type | Screw |
Contact Configuration | 3P-NO |
Output Device | Phototriac Coupler |
Maximum Turn On Time | 1/2 cycle + 1 ms |
Series | G3PE Three Phase |
Load Voltage Range | 180 → 528V ac |
Dimensions | 110 x 155 x 140mm |
Height | 140mm |
Off State Leakage Current | 20 mA |
Length | 110mm |
Maximum Operating Temperature | +80°C |
Operating Temperature Range | -30 → +80°C |
Depth | 155mm |