Jumo 701155 DIN Rail Controller 2 Input, 4 Output Analogue 30V ac/dc Controller

Subtotal (1 unit)*

SGD1,378.01

(exc. GST)

SGD1,502.03

(inc. GST)

Add to Basket
Select or type quantity
Temporarily out of stock
  • Shipping from 03 April 2026
Need more? Click ‘Check delivery dates’ to find extra stock and lead times.
Units
Per unit
1 +SGD1,378.01

*price indicative

RS Stock No.:
279-257
Mfr. Part No.:
701155/8-01-0253-2001-25-044-005/059,000
Manufacturer:
Jumo
Find similar products by selecting one or more attributes.
Select all

Brand

Jumo

Product Type

Controller

Output Type

Analogue

Number of Inputs

2

Number of Outputs

4

Maximum Current

3A

Minimum Operating Temperature

0°C

Maximum Operating Temperature

55°C

Terminal Type

Screw

Control Type

Controller

Maximum Supply Voltage

30V ac/dc

Auxiliary Power Supply

110/240 V ac

Digital Comms

USB Interface

Diagnostics

Yes

Maximum Voltage

250V

Display Type

LCD Backlight

IP Rating

IP20

Width

45 mm

Standards/Approvals

IECEX, UKCA, SIL 3, PL e, ATEX, DIN EN 13849, DIN EN 14597, DIN EN 50495, DIN EN 61508, DIN EN ISO 80079-37, EAC Ex, DNV

Length

104.8mm

Input Type

Analogue

Series

701155

Mount Type

DIN Rail

Panel Depth

85mm

COO (Country of Origin):
DE
The Jumo Ex Safety temperature limiter and monitor according to DIN EN 14597 has a power supply range of AC/DC 20 to 30 V, 48 to 63 Hz. The compact and user configurable JUMO safetyM STB/STW Ex can now also enable early and reliable detection of risks in Ex-areas which could potentially result in personal injuries, environmental damage, or destruction of the production plant and production materials. The devices are available in 2 versions. 1-sensor version Ex II (1) (2) (3) G (b1) [Ex ia Ga] [e pz] IIC , Ex II (1) (2) (3) D (b1) [Ex ia Da] [p Dc] IIIC. 2-sensor version Ex II (1) (1) (2) G (b2) [Ex ia Ga] [e py] IIC, Ex II (1) (1) (2) D (b2) [Ex ia Da] [p Db] IIIC. The primary task of safety temperature limiters is to reliably monitor thermal processes and to switch plants to a safe operating status in the event of malfunctions. Along with the existing approvals according to DIN 14597, SIL 3, PL e and GL.

Inputs are intrinsically safe allowing direct connection of relevant probes without barriers

Certified to DIN EN 50495 and DIN EN 13463-6 as an ignition source monitoring device

Meets DIN EN 61508 and DIN EN 13849 requirements for safety applications

1oo2D structure ensures fault detection and compliance with Machinery Directive 2006/42/EC

Backlit display with plain text for quick and easy configuration and clear menu structure

Displays all safety relevant process values with simple pictograms

Two universal analogue inputs and one digital input

Two relay outputs and one universal analogue output

Approval according to ATEX and can therefore also be used for measurements in Ex areas

Related links