Legislation and Compliance
- COO (Country of Origin):
- DE
Product Details
FLASHTRAB-PLUS surge protectors
Type 1 / Class I/B pluggable lightning surge protector designed to be placed on the main power supply in a low-voltage installation of a building protected by a lightning rod.
These pluggable arresters feature a high absorption capacity of 50 KA.
Unplugging the module does not require line cut-off.
Models FLT-CP-PLUS-…S... are designed for applications in which the ground (PE) and neutral (N) are separate, and FLT-CP-PLUS-…C..models are designed for applications in which the ground and neutral are common.
Mechanical display on each module.
Remote signalling contact for remote status display.
For mounting on DIN rail.
Screw connection.
These pluggable arresters feature a high absorption capacity of 50 KA.
Unplugging the module does not require line cut-off.
Models FLT-CP-PLUS-…S... are designed for applications in which the ground (PE) and neutral (N) are separate, and FLT-CP-PLUS-…C..models are designed for applications in which the ground and neutral are common.
Mechanical display on each module.
Remote signalling contact for remote status display.
For mounting on DIN rail.
Screw connection.
Surge Protection Devices, SPDs (DIN-rail)
Voltage surges, often referred to as spikes or transients are typically caused by switching of fluorescent lights, fuses blowing or nearby lightning activity. The worst voltage surges are usually caused by lightning and can reach up to 6000V, with current surges of over 3000A. The maximum size of the voltage and current surges depends on the location within the building's wiring system. BS7671: 2011 Amendment 1 Sections 443 and 534 cover risk assessment and provides guidance on protection of electronic equipment for installation engineers to follow. The fullest information on lightning and surge protection comes from the BSEN 62305 series of standards.
Specifications
Attribute | Value |
---|---|
Device Type | Surge Protector |
Voltage Protection Rating | 250V ac |
Series | FLT-CP-PLUS-1S-350 |
Mounting Style | DIN Rail |
Impulse Discharge Current | 25kA |
Length | 95.8mm |
Width | 71.6mm |
Depth | 70mm |
Dimensions | 95.8 x 71.6 x 70mm |
Minimum Operating Temperature | -40°C |
Maximum Operating Temperature | +80°C |