- RS Stock No.:
- 361-1596
- Mfr. Part No.:
- 45225 230VAC
- Manufacturer:
- Broyce Control
Discontinued product
- RS Stock No.:
- 361-1596
- Mfr. Part No.:
- 45225 230VAC
- Manufacturer:
- Broyce Control
Legislation and Compliance
- COO (Country of Origin):
- GB
Product Details
Liquid Level Controller
Controls maximum and/or minimum levels of conductive liquids
Pump-up or Pump-down modes selectable via switch
Adjustable sensitivity 5-100kΩ
Response times 100ms (high level); 500ms (low level)
One or two probe operation
Low voltage, ac current across probes prevents electrolysis phenomena
LED indication for supply and relay status
Ambient temperature; -20 to +60°C
DIN rail mounting, W45mm
Write-on identification tab
Dimensions (mm): H 75, W 45, D 99
Pump-up or Pump-down modes selectable via switch
Adjustable sensitivity 5-100kΩ
Response times 100ms (high level); 500ms (low level)
One or two probe operation
Low voltage, ac current across probes prevents electrolysis phenomena
LED indication for supply and relay status
Ambient temperature; -20 to +60°C
DIN rail mounting, W45mm
Write-on identification tab
Dimensions (mm): H 75, W 45, D 99
Note
1. If using metal tank, connect com and earth to the tank
2. If supply is interrupted for ≤0.5s in pump-up mode, the relay will energise immediately. In pump-down mode relay remains de-energised
3. For single probe operation, link terminals com and max
2. If supply is interrupted for ≤0.5s in pump-up mode, the relay will energise immediately. In pump-down mode relay remains de-energised
3. For single probe operation, link terminals com and max
Liquid Level Relays are used to monitor the levels of conductive liquids, and are available in Up/Down, Minimum, Maximum, and Fill/Empty variations. Liquid Level Relays are straightforward to install and safe to use.
Application Examples
Liquid Level Relays (Conductive Level Sensors) are used in a wide variety of applications including waste water management and the monitoring and management of corrosive liquid media, and designed specifically to provide for the:
Monitoring and control of liquid levels
Protection of pumps against dry running
Ability to detect liquid leaks in a system
Control of media mixing ratios
Control of liquid levels
Protection of pumps against dry running
Ability to detect liquid leaks in a system
Control of media mixing ratios
Control of liquid levels
Specifications
Attribute | Value |
---|---|
Number of Inputs | 1 |
Mounting Style | DIN Rail Mount |
Probe Voltage | 17V ac |
Supply Voltage | 230 V ac |
Overall Length | 78mm |
Overall Width | 45mm |
Overall Depth | 99mm |
Minimum Operating Temperature | -20°C |
Maximum Operating Temperature | +60°C |