ETA Busbar, 24V dc, 500mm Pitch

  • RS Stock No. 723-4862
  • Mfr. Part No. X222.611.02 GREY BUSBAR (500MM)
  • Manufacturer ETA
Technical data sheets
Legislation and Compliance
RoHS Certificate of Compliance
COO (Country of Origin): DE
Product Details

ESX10-T Electronic Circuit Protectors

Electronic circuit protector type ESX10-T is designed to ensure selective disconnection of DC24V load systems. By active current limitation, ESX10-T responds much faster to overload or short circuit conditions than switch-mode power supply. The ESX10-T limits the highest possible current to 1.3 to 1.8 times the selected rated current of the circuit protector. It is therefore possible to switch on capacitive loads of up to 20,000μF, but they are disconnected only in the event of an overload or short circuit.

Selective load protection, electronic trip characteristics
Reliable overload disconnection with 1.1 x lN plus, even with long load lines or small cable cross sections
Manual ON/OFF button (S1)
Status and failure indication through LED, status output SF or Si contact F
Integral fail-safe element adjusted to current rating
Can be snapped onto symmetrical rails for ease of installation and space-saving in control cabinets
Ease of wiring through busbar LINE+ and 0 V as well as signal bars and bridges

Approvals

UL, CSA

Approvals

UL, CSA

Specifications
Attribute Value
Rated Operational Voltage 24V dc
Current Rating 500 mA
Pitch 500mm
13 In stock for delivery within 4 working days
Price Each
SGD 120.96
(exc. GST)
SGD 129.43
(inc. GST)
units
Per unit
1 - 9
SGD120.96
10 - 24
SGD118.63
25 - 49
SGD116.64
50 - 99
SGD115.46
100 +
SGD114.29
Related Products
Splitters for XE plug-in technology.A connector combined with ...
Description:
Splitters for XE plug-in technology.A connector combined with a splitter supplies two rows. stock no. 145-279.Rated operating current: 63 A @ 40 °C.Rated insulating voltage: 250 VacMounting on support provided at the back of the symmetrical rail on Opale and ...
Type B characteristic offers instantaneous short circuit response ...
Description:
Type B characteristic offers instantaneous short circuit response level of 3-5 x normal rated current, making it suitable for circuits with moderate inrush currents such as filament lamps, heating loads and most domestic/small building protection applications.,Type C characteristic offers short ...
Three-phase busbar systems provide an easy, time-saving and ...
Description:
Three-phase busbar systems provide an easy, time-saving and clearly arranged means of feeding 3RV2 motor starter protectors with screw terminals. The system can be used with various types of motor starter protectors up to 32 A. The 3RV19 15 three-phase ...
ESS20 electronic circuit breaker designed to selectively protect ...
Description:
ESS20 electronic circuit breaker designed to selectively protect individual circuits powered from single switch-mode power supplies (SMPS). Easily added to a DIN/EN rail, the ESS20 provides advanced circuit protection for components used in factory automation systems. Switchable current rating ranges ...